Permit Number: T04CM02682
Parcel: 11714096A

Address:
460 S 6TH AV

Review Status: Completed

Review Details: REVISION - - 5TH

Permit Number - T04CM02682
Review Name: REVISION - - 5TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/28/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide revised sheet M-P1.12. Reference Section 103.2.3, UPC 1994.
2. Revise the waste from the clotheswasher located in room 1111 from 2' to 3" to comply with the listing information from the manufacturer of the air admittance valve. Reference Section 909.1.1, UPC 1994 (State amendments).
3. Provide an expansion tank for water heater WH-2. Reference Section 608.3, UPC 1994.
4. Show how WH-2 is to be supported from the building structure. Reference Section 314.5, UPC 1994.
5. Limit the use of the air admittance valves to vent fixtures that are on the same floor. Reference Section 909.1.3, UPC 1994 (State amendments).
03/28/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the dryer exhaust terminations for rooms 1101, 1102, 1103, and 1104 are not located so as to create a nuisance. Reference Section 501.3, IMC 2000
2. Clarify how Mechanical Keynote #4 and Mechanical General Note #9 are coordinated. Reference Section 106.3.1, IMC 2000.
3. Bathroom exhaust ducts may not be terminated in an attic. Reference Section 501.3, IMC 2000.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/29/2006 BETH GRANT OUT TO CUSTOMER Completed
03/29/2006 SUE REEVES REJECT SHELF Completed