Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM02626
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/10/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/10/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Use Table 6-4 to determine the water pipe sizes. Revise sizes as required. Reference Section 610.4, UPC 1994. 2. A mop basin with a 3" trap is rated at 6 waste fixture units. |
| 06/10/2004 | NEAL SAUNDERS | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 06/10/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/10/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 06/10/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the weight of the fan powered HEPA filter unit and show how it is to be supported. 2. Clarify how HP-1 is to be balanced (unit scheduled at 800 cfm, delivers 1200 cfm). 3. Revise the ventilation calculations for HP-1 using the occupant loads from Table 403.3, IMC 2000 (Workroom - Pharmacy). 4. Correct occupant load information for HP-2 (Storage and Toilet). Note: the lobby should be classified as "retail - Basement and Street" rather than "Hotel - Lobby". Use Section 403.3.2 to determine corrected minimum ventilation flow rate. |
| 06/10/2004 | NEAL SAUNDERS | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 06/10/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 06/11/2004 | CAGUILA1 | WWM | REVIEW | Needs Review |