Permit Number: T04CM02626
Parcel: 110055290

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02626
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2004 JIM EGAN FIRE REVIEW Approved
06/10/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Use Table 6-4 to determine the water pipe sizes. Revise sizes as required. Reference Section 610.4, UPC 1994.
2. A mop basin with a 3" trap is rated at 6 waste fixture units.
06/10/2004 NEAL SAUNDERS BUILDING-COMMERCIAL REVIEW Needs Review
06/10/2004 ROBERT SHERRY WATER REVIEW Approved
06/10/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
06/10/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the weight of the fan powered HEPA filter unit and show how it is to be supported.
2. Clarify how HP-1 is to be balanced (unit scheduled at 800 cfm, delivers 1200 cfm).
3. Revise the ventilation calculations for HP-1 using the occupant loads from Table 403.3, IMC 2000 (Workroom - Pharmacy).
4. Correct occupant load information for HP-2 (Storage and Toilet). Note: the lobby should be classified as "retail - Basement and Street" rather than "Hotel - Lobby". Use Section 403.3.2 to determine corrected minimum ventilation flow rate.
06/10/2004 NEAL SAUNDERS ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/10/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
06/11/2004 CAGUILA1 WWM REVIEW Needs Review