Permit Number: T04CM02625
Parcel: 133243700

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02625
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2004 JIM EGAN FIRE REVIEW Approved
06/10/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the scope of plumbing work for this project. Reference Section 103.2.3, UPC 1994.
06/10/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
06/10/2004 ROBERT SHERRY WATER REVIEW Approved
06/10/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide sufficient information to demonstrate that the ventilation flow rates comply with Section 403.3.2, IMC 2000.
06/11/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
06/11/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/11/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
06/17/2004 DROBEY1 WWM REVIEW Needs Review