Permit Number: T04CM02608
Parcel: 12009214B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02608
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2004 Terry Stevens BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T04CM02608
9/7/04
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

NOTE: SEVERAL AREAS OF THE PLANS ARE NOT LEGIBLE. PRINTING IS TO SMALL TO READ. PLEASE USE LARGER FONT. [DETAILS, ELECTICAL,]

SITE PLAN:

1. INDICATE THE LOCATION OF GAS METERS AND GAS LINES. AS INDICATED DOES NOT MATCH WITH PLUMBING PLAN FOR DEVELOPED LENGTH.

FOUNDATION PLANS:

1. DIMENSION THE FOOTING THICKNESS AND DEPTH INTO UNDISTURBED SOIL FOR EACH FOOTING TYPE AND CONDITION PER TABLE R403.1.

2. ALL SLABS AND PADS, INCLUDING LANDINGS AT ALL DOORS, SHALL BE SHOWN AND THEIR THICKNESS
SPECIFIED. INDICATE THE SLOPE FOR EXTERIOR SLABS, PER R312.

STRUCTURAL PLANS:

1. MASONRY LINTELS REQUIRE A DESIGN BY A ENGINEER. THERE IS NOT 32" ABOVE ANY OF THE OPENINGS FOR LINTEL INDICATED. SUGGEST USING ANGLE IRON LINTELS. SPECIFY SIZE AND LOCATION.

2. DETAIL GABLE END BRACING CONNECTIONS.

3. COMPLETELY DETAIL ALL CONNECTIONS AND CROSS-REFERENCE TO THE FOUNDATION AND FRAMING
PLANS.

SECTIONS - DETAILS - MISC. NOTES:

1. WOOD SILL PLATES SHALL BE FOUNDATION GRADE REDWOOD OR PRESSURE-TREATED WOOD PER R324.
AT FUR OUT

2. CROSS-SECTIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLAN AND FRAMING PLANS.

PLUMBING PLANS:

1. PROVIDE AN ISOMETRIC DRAWING OF WASTE LINES. SHOW SIZES OF WASTE LINES, VENTS AND REQUIRED
CLEANOUTS.

2. GAS: PROVIDE THE LENGTH OF LINE TO EACH APPLIANCE, BTU DEMAND OF EACH APPLIANCE, SIZE OF
EACH BRANCH, TOTAL DEMAND & TOTAL DEVELOPED LENGTH FROM METER TO MOST REMOTE
APPLIANCE ON THE SYSTEM PER UPC 1217.2

3. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH---------AS PER 1994 UPC WITH STATE AMENDMENTS, NOT THE IRC 2000.

4. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS
AND SHOWERHEADS 3 GALLONS PER MINUTE.

5. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER.

6. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL
VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE.

7. THE CITY OF TUCSON HAS NOT ADOPTED THE PLUMBING SECTION OF THE IRC 2OOO. THE CURRENT CODE BEING USED IS THE 1994 UPC WITH THE STATE AMENDMENTS. ALL PLANS MUST REFERENCE TO THIS CODE.

8. ½" WATER LINES TO BATHROOM AND KITCHEN FIXTURES INADEQUATE.

9. PROVIDE REQUIRED CLEAN OUTS AS PER 1994 UPC AT FIXTURES.

10. HORIZONTAL WASTE FOR DISHWASHER, MIN. SIZE IS 2". VENT IS MISSING.

MECHANICAL PLANS:

1. PLANS INDICATE A GAS/A/C UNIT, MECH. CALL OUTS INDICATE SPLIT SYSTEM------CLARIFY. BTU'S ON CALL OUT DO NOT MATCH PLUMBING PLAN.

2. DUCT SIZING FOR SUPPLY AND RETURN AIR DOES NOT MIN. CODE. 6 SQ. IN. PER 1000 BTUS FOR A/C.

ELECTRICAL PLANS:

1. ELECTRICAL FOR WATER HEATER? NOT ON PLANS, CALCS, OR PANEL SCHEDULE.

2. CALCS SHOW HEAT PUMP? 30 AMP NOT LARGE ENOUGH FOR 5 TON A/C AS PER MECH PLAN------CLARIFY

3. NOTE THE GROUNDING AND BONDING METHOD FOR SERVICE PANEL.

4. RECEPTACLE OUTLETS SHALL BE PROVIDED AT EACH KITCHEN COUNTER SPACE WIDER THAN 12", AND
SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24" FROM A RECEPTACLE
OUTLET, PER E3801.4.1

5. ISLAND OR PENINSULA COUNTER TOPS SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET AT EACH
COUNTER SPACE WITH A LONG DIMENSION OF 24" OR GREATER, AND A SHORT DIMENSION OF 12" OR
GREATER, PER E3801.4.2 AND E3802.4.3.

6. ALL RECEPTACLE OUTLETS IN BATHROOMS, KITCHENS, UNFINISHED BASEMENTS, GARAGES OR CARPORTS,
AT GRADE LEVEL AND WITHIN 6' OF A WET BAR OR KITCHEN SINK SHALL HAVE GROUND FAULT CIRCUIT
INTERRUPTING PROTECTION. NOTE ON THE DRAWINGS AT EACH OUTLET REQUIRING SUCH PROTECTION,
PER E3802.

7. TWO OR MORE 2OAMP SMALL APPLIANCE CIRCUITS SHALL BE PROVIDED TO SERVE ALL RECEPTACLE OUTLETS AT THE KITCHEN COUNTERS, BREAKFAST ROOM AND DINING ROOM. SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS, PER E3603.2 AND E3801.3-4.5.

MODEL ENERGY CODE:

1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11.
CALCS ARE NOT CORRECT------R-52 @ CEILING?-----R-26 @ WALLS?-------R-13 @ FLOOR?
PROVIDE CALCS FOR ENTIRE BLDG. NOT JUST 3 WALLS OF ONE HALF OF THE STRUCTURE

2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS
AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 1112

Final Status

Task End Date Reviewer's Name Type of Review Description
09/10/2004 DELMA ROBEY OUT TO CUSTOMER Completed