Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM02585
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/25/2005 | Neil Saunders | BUILDING-RESIDENTIAL | REVIEW | Denied | 1. Wood headers are required in framed (wood) bearing walls. These walls occur on two interior walls. Lintels over windows and doors in Mikey block walls (exterior) are per Lintel design set forth on lintel details. 2. 6/4 - Discrepancy with callout on plans. HUS212 is for a 2x12 rafter yet porch roof framing is 2x6. Clarify. 2x6 ledger is all that is required for 2x6 rafters. 3. Callout spacing of ICFLC-W for all ledgers. 4. Section B-B - Insulation cannot be on underside of turret roof if shingles are used. Also, provide ventilation for this attic space. 5. Parapet on back porch is not shown on elevations. Clarify. 6. Provide connection details for all wood beams that connect to Mikey block walls. 7. 7/4 - APS6 under 10" post seems inadequate. Consider PBV10PC with or without purlin anchors. 8. Garage - 5/5 - MBHA5.50 is not suitable for Mikey block. Provide a beam pocket and beam seat or lintel design. 9. Provide two copies of truss calcs. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/27/2005 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 01/27/2005 | SUE REEVES | REJECT SHELF | Completed |