Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM02552
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/07/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 06/08/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/09/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/09/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/09/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise ventilation calculations to show how much outside air is being supplied to each room. Adjust ventilation quantities as required using method shown in ection 403.3.2, IMC 2000. 2. Show the exhaust flow rates for the two restrooms. Reference Section 403.3, IMC 2000. |
| 06/10/2004 | NEAL SAUNDERS | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 06/17/2004 | LLESNY1 | WWM | REVIEW | Needs Review | |
| 06/17/2004 | LLESNY1 | ENGINEERING | REVIEW | Needs Review | |
| 06/17/2004 | LLESNY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/17/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |