Permit Number: T04CM02544
Parcel: 117040970

Address:
639 N 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02544
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2005 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
01/10/2005 Peter McLaughlin ZONING REVIEW Denied SITE PLAN TRANSMITTAL

TO: Kevin Palmer -The Architecture Company
2625 N. Silverbell Road
Tucson, AZ 85745
(520) 622-4506

FROM: Peter McLaughlin
Senior Planner


FOR: Patricia Gehlen
Principal Planner
Development Services Dept.

PROJECT:
T04CM02544
Desert Institute For Healing Arts
639 N. 6th Avenue
Site Plan Review (2nd review)

TRANSMITTAL: January 11, 2005

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. It is acknowledged in response comment #4 and in the vehicle parking calculation that there is not sufficient parking provided on site for the proposed educational-instructional school use. A Board of Adjustment Variance is required for the parking deficit. State the variance case number, date of approval, what variances were approved for and conditions of approval on the site plan. In addition, provide a copy of the variance approval document to the Zoning Review Section upon resubmittal.
DS 2-02.2.1.A.3
DS 2-02.2.1.A.38

2. It is acknowledged in response comment #12 and in the calculations that no loading zone is to be provided. A Board of Adjustment variance application must be approved. See comment 1 regarding BOA variance requirements.
DS 2-02.2.2.A.5

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
12/08/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the scope of work for the second floor. Reference Section 103.2.3, UPC 1994.
2. Note: Traps will not be required for the showers connected to the sand interceptor provided the interceptor has a water seal of at least 6" and is vented.
12/08/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/15/2004 BLANCA ESPINO ENGINEERING REVIEW Denied Site Plan
1. Recyclable pick-up can be discontinued. Commercial and residential establishments are required to have refuse containers regardless if public or private. Indicate refuse container location, size and access thereto fully dimensioned. D.S. 2-02.32 Demonstrate vehicle maneuverability fully dimensioned. Indicate a refuse enclosure detail as per D.S. 6-01.4.2 Contact John Clark of Environmental Services @ 791-3175 ext. 1136 to reach an agreement that does not meet Development Standards 6-01 and to obtain a DSMR.
12/20/2004 Gerry Koziol WWM REVIEW Denied Needs WW credit evaluation.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/21/2005 TAMI ACHONG OUT TO CUSTOMER Completed
01/21/2005 TAMI ACHONG REJECT SHELF Completed