Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM02540
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/07/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 06/07/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/07/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/07/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/07/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise outside air calculations for new AC unit and existing 3.5-ton unit to comp[ly with the requirements of Section 403.3.2, IMC 2000. |
| 06/15/2004 | TACHONG1 | ZONING | REVIEW | Needs Review | |
| 06/15/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/15/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM02540 DENIED 6/10/04 1. Phase C, at 26.6 KV, would carry 222A, which would overload the 200A panel. Please rebalance. 2. Please provide for overload protection on CU-1 and AC-1, or justify otherwise. |
| 06/15/2004 | TACHONG1 | FIRE | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/15/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |