Permit Number: T04CM02540
Parcel: 120070570

Address:
301 W AJO WY

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02540
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2004 JIM TATE ENGINEERING REVIEW Approved
06/07/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/07/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
06/07/2004 ROBERT SHERRY WATER REVIEW Approved
06/07/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise outside air calculations for new AC unit and existing 3.5-ton unit to comp[ly with the requirements of Section 403.3.2, IMC 2000.
06/15/2004 TACHONG1 ZONING REVIEW Needs Review
06/15/2004 GERRY KOZIOL WWM REVIEW Approved
06/15/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM02540 DENIED 6/10/04

1. Phase C, at 26.6 KV, would carry 222A, which would overload the 200A panel. Please rebalance.
2. Please provide for overload protection on CU-1 and AC-1, or justify otherwise.
06/15/2004 TACHONG1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/15/2004 TAMI ACHONG OUT TO CUSTOMER Completed