Review Details: COMMERCIAL TI

Permit Number - T04CM02539
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2004 JIM EGAN FIRE REVIEW Approved
06/07/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide riser diagram for the water piping.
2. Size the water piping using Table 6-4 (<50 fixture units, < 200 Feet). Reference Section 610.4, UPC 1994.
3. Include all water fixtures in the fixture unit calculations. Reference Section 610.1, UPC 1994.
4.Verify that the size of the existing RPBP is 1-1/2". Reference Section 610.2, UPC 1994.
5. Revise waste fixture unit tabulation; a mop sink with a 3" trap is rated at 6 waste fixture units. Reference Tale 7-3, UPC 1994.
06/07/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
06/07/2004 ROBERT SHERRY WATER REVIEW Approved
06/07/2004 JIM TATE ENGINEERING REVIEW Approved
06/07/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the ventilation calculations
a. use net area of each room for the calculations.
b. Correct the total outside air for each AC unit using Section 403.3.2, IMC 2000.
06/10/2004 NEAL SAUNDERS BUILDING-COMMERCIAL REVIEW Needs Review
06/10/2004 TACHONG1 WWM REVIEW Needs Review
06/10/2004 NEAL SAUNDERS ELECTRICAL-COMMERCIAL REVIEW Needs Review