Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM02539
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/07/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/07/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide riser diagram for the water piping. 2. Size the water piping using Table 6-4 (<50 fixture units, < 200 Feet). Reference Section 610.4, UPC 1994. 3. Include all water fixtures in the fixture unit calculations. Reference Section 610.1, UPC 1994. 4.Verify that the size of the existing RPBP is 1-1/2". Reference Section 610.2, UPC 1994. 5. Revise waste fixture unit tabulation; a mop sink with a 3" trap is rated at 6 waste fixture units. Reference Tale 7-3, UPC 1994. |
| 06/07/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 06/07/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/07/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 06/07/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the ventilation calculations a. use net area of each room for the calculations. b. Correct the total outside air for each AC unit using Section 403.3.2, IMC 2000. |
| 06/10/2004 | NEAL SAUNDERS | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 06/10/2004 | TACHONG1 | WWM | REVIEW | Needs Review | |
| 06/10/2004 | NEAL SAUNDERS | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |