Permit Number: T04CM02530
Parcel: 13419042D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02530
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
06/04/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
06/07/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide Cleanout for both P-5 sinks.
2. Show how the water piping was sized.
3. Clarify where the T&P relief is to be terminated.
06/07/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
06/07/2004 ROBERT SHERRY WATER REVIEW Approved
06/07/2004 JIM EGAN FIRE REVIEW Approved
06/07/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Correct the ventilation calculations (25 cfm required per person in a beauty shop). Reference Section 403.3,IMC 2000.
06/08/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/11/2004 CAGUILA1 WWM REVIEW Needs Review