Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM02530
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/04/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 06/04/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 06/07/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide Cleanout for both P-5 sinks. 2. Show how the water piping was sized. 3. Clarify where the T&P relief is to be terminated. |
| 06/07/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/07/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/07/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/07/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Correct the ventilation calculations (25 cfm required per person in a beauty shop). Reference Section 403.3,IMC 2000. |
| 06/08/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/11/2004 | CAGUILA1 | WWM | REVIEW | Needs Review |