Permit Number: T04CM02520
Parcel: 12002041A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02520
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2004 JIM EGAN FIRE REVIEW Denied 2-hour fire barrier required between A-2 & B Occupancies for separated uses.
06/04/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise waste piping to limit the maximum developed length of the water closet trap arm to less than 6 feet. Reference Table 10-1, UPC 1994.
2. Coordinate the callout for the water heater - P-3 or WH-1.
06/04/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/04/2004 ROBERT SHERRY WATER REVIEW Approved
06/04/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show outside air calculations.
2. Provide a minimum of 75 cfm exhaust for the rest room.
3. Show the size, route, and termination of the condensate drains from the RTU's.
06/09/2004 DROBEY1 ZONING REVIEW Needs Review
06/09/2004 DROBEY1 WWM REVIEW Needs Review
06/09/2004 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
06/09/2004 DROBEY1 ENGINEERING REVIEW Needs Review