Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM02520
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/04/2004 | JIM EGAN | FIRE | REVIEW | Denied | 2-hour fire barrier required between A-2 & B Occupancies for separated uses. |
| 06/04/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise waste piping to limit the maximum developed length of the water closet trap arm to less than 6 feet. Reference Table 10-1, UPC 1994. 2. Coordinate the callout for the water heater - P-3 or WH-1. |
| 06/04/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 06/04/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/04/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show outside air calculations. 2. Provide a minimum of 75 cfm exhaust for the rest room. 3. Show the size, route, and termination of the condensate drains from the RTU's. |
| 06/09/2004 | DROBEY1 | ZONING | REVIEW | Needs Review | |
| 06/09/2004 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 06/09/2004 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 06/09/2004 | DROBEY1 | ENGINEERING | REVIEW | Needs Review |