Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T04CM02519
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/23/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TO4CM02519 DENIED 9/23/04 1. Please increase font size for bollards to 10 point. Sheet E1. 2. Provide panel schedule for the panel serving the exterior lighting fixtures. Provide feeder and service load calculations. This shall be included in the drawings sealed by the Registered Electrical Engineer for the exterior lighting project. Reflect proper voltage level per the Luminaire Schedule on Sheet E2C. Reflect correct circuit numbers per Sheet E1. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/23/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |