Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T04CM02519
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/15/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
09/15/2004 | DAVE MANN | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
09/15/2004 | DAVE MANN | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/15/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
09/16/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
09/16/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
09/16/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/17/2004 | DAVE MANN | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM02519 DENIED 9/17/04 1. Minimum font size is 10 point, which is a little over 1/8". 2. Please provide cut sheets for Fixtures R1 and S. Will verify compliance with Outdoor Lighting Ordinance for both fixtures and will verify Fixture R1 is listed for wet locations. 3. Provide panel schedule for the panel serving the exterior lighting fixtures. Provide feeder and service load calculations. |
09/23/2004 | CRAIG GROSS | ZONING | REVIEW | Approved |