Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - COMM
Permit Number - T04CM02519
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/04/2004 | PATRICIA GEHLEN | ZONING | REVIEW | Needs Review | |
06/16/2004 | CAGUILA1 | FIRE | REVIEW | Approved | |
06/16/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
06/16/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Needs Review |