06/29/2004 Christy Foreman BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS PROJECT #T04CM02516
06/30/2004 9231 E. Old Spanish Tr.

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.
SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical. All code references are to the 2000 International Residential Code, 2000 International Energy Conservation Code, and Arizona State Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
GENERAL REQUIREMENTS:
1. All plans shall be legible and a scale no smaller than ¼ inch = 1-foot shall be used for all floor plans, framing plans and elevations. Details and cross sections shall be a minimum 3/8 inch = 1-foot scale.
2. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia & (1) blue line shall be returned along with all redline prints. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
3. List the square footage for all the following areas separately on the drawings:
- Livable area
- garage
- porch / patio covers
- decks
SITE PLAN:
1. Provide copy of approved site plan show previously permitted pool house.
2. Indicate the location of gas, water, electric and sewer or septic line on the property, and where they enter the building. Provide the location of your water meter and septic system if it exists.
FOUNDATION PLANS:
1. Note on the drawings the allowable soil bearing pressure used in the design of the footings, or state that the assumed value of 1500 PSF is being used per table R401.4.1, a soils report is not required. It is up to the designer / homebuilder to be aware of the soil and conditions of the site. If soil testing has been done, a copy of the soils report shall be submitted with the construction plans, and the foundation design shall reflect the soils reports recommendations.
2. Dimension the wall thickness, footing width thickness and depth into undisturbed soil for each footing type and condition per IRC table R403.1. Footing between Garage and hallway?
FLOOR PLANS:
1. Per R309.2. 20 min. rated door at garage / hallway door.
STRUCTURAL PLANS:
Consider eliminating glulam beams and span wall to wall with TJI's.
1. Completely detail all connections and cross-reverence to the foundation and framing plans:
- Section 1 - how will ledger be attached to existing / masonry need a thru-bolt.
- Section 1 - Clarify size of ledger bolt.
- Size lintels at all openings in walls.
- Section 3 - Trusses to top plate
- Clarify how saddle embeds are in grouted cells. Glulam beam @ masonry connection must have ½" air gap top & bottom per IBC 2304.11.2.4
- Section 2 lag bolts required. Nailing is not adequate.
- Section 2 - ledger must be 3x per code section R606.10 or PA strap per IBC 2109.7.3.1.
- Clarify F2 footing & section 1 - height of wall bond beam location.
- Clarify TJI.
- Clarify F1 footing & section 2 - height of wall bond beam location.
ELEVATIONS:
1. Provide complete drawings of all elevations. Include patio covers, decks, fireplaces and bay windows. Show building heights.
2. Indicate all materials used; stucco, concrete block, glass block, roofing system, siding, veneer, etc.
3. Note and specify a complete roofing system: Roofing type, grade of materials and method of installation per R905.
4. Note and specify all roof slopes appropriate to material. (minimum allowable roof slope is ¼" per foot per R905)
5. Note and size all roof drains or scuppers on flat roofed areas per R903.4.
6. Show calculation of attic ventilation area in compliance with R806.2. Note location of all vents needed to comply.
7. Note and dimension that the fireplace chimney must terminate a minimum of 2' above any point of roof within 10' measured horizontally and not less than 3' above the point where the chimney passes through the roof, per R1001.6.
8. Note glass in hazardous areas shall be safety glass per 308.4.
9. For veneer, note and specify type of veneer. Provide detail and specify anchoring method, backing, vapor barrier and support per R301.2.2.3.
10. For thin-coat stucco systems over foam board, note and specify the ICBO evaluation report number, system name and manufacturer, note and specify the vapor barrier.
11. Foam insulation: Clarify your compliance with R318 on the main walls and those walls to the attic per R318.2.3.
12. Specification / size for steel beam at garage door?
If you have any questions, please contact your assigned plans examiner Christy Foreman at 791-5550, extension 1113.