Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM02482
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/28/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the water piping shown on detail 4/MP1.0 to correspond to the calculations shown on sheet MP2.0. The calculations indicate that the main supply is undersized. Reference Section 610.1, UPC 1994. |
| 07/09/2004 | TACHONG1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/09/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |