Permit Number: T04CM02482
Parcel: 11206013A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02482
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide calculations to show that the existing 3/4" water line is capable of supporting the new load. Note: the maximum permissible velocity for copper pipe is 8 fps. Reference Section 610.0, IAPMO IS 3-93.
06/18/2004 ROBERT SHERRY WATER REVIEW Approved
06/18/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/21/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/24/2004 TACHONG1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/24/2004 TAMI ACHONG OUT TO CUSTOMER Completed