Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM02482
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/03/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/03/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 06/03/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 06/04/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide calculations to show that the existing 3/4" water line is capable of supporting the new load. 2. Revise the waste piping for P-1 in the restroom to avoid a wet vent connection. |
| 06/04/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/04/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show the amount of outside air to be provided to the space. |
| 06/07/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM02402 DENIED 6/7/04 1. Water Heater, on a 2-P CB, should have its 4000 W distributed between Phases A and B. 2. Phase B appears to total 11, 391, not 7791. |
| 06/18/2004 | TACHONG1 | WWM | REVIEW | Needs Review | |
| 06/18/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/18/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |