Permit Number: T04CM02482
Parcel: 11206013A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02482
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2004 JIM EGAN FIRE REVIEW Approved
06/03/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
06/03/2004 JIM TATE ENGINEERING REVIEW Approved
06/04/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide calculations to show that the existing 3/4" water line is capable of supporting the new load.
2. Revise the waste piping for P-1 in the restroom to avoid a wet vent connection.
06/04/2004 ROBERT SHERRY WATER REVIEW Approved
06/04/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show the amount of outside air to be provided to the space.
06/07/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM02402 DENIED 6/7/04

1. Water Heater, on a 2-P CB, should have its 4000 W distributed between Phases A and B.
2. Phase B appears to total 11, 391, not 7791.
06/18/2004 TACHONG1 WWM REVIEW Needs Review
06/18/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/18/2004 TAMI ACHONG OUT TO CUSTOMER Completed