Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM02477
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/02/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 06/04/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/04/2004 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 06/04/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/04/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/08/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/08/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/08/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/08/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM02477 DENIED 6/4/04 1. Refrigerator Condensor, on Ckt W-5,7, shall have max fuse size is 15A according to catalogue, not 20. 2. Freezer Condensor, on Ckt W-1,3, shall have max fuse size is 35A according to catalogue, not 40. 3. Specify conductor size for Freezer Condenser. |