Permit Number: T04CM02457
Parcel: 13510150R

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02457
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2000, for mercantile occupancy.
07/09/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/20/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. Clarify metering nomenclature. New meters are called M-2 and M-3 on Single Line Diagram. They are called T2 and T3 on the load study.

2. Since there are 2 new meters, they both have to be accounted for in our computerized system, Permits Plus. Applicant shall to go to Pima County addressing, obtain addresses for both meters by specific designation per Comment #1 above, and then present them to Development Services for addition into our system.

3. First review found that Ckt NTB-28 had load indicated on the power plan but not on the panel schedule. Response indicated that the designation "NTB-28" should have read "NTA-37". Upon second review it has been determined that "NTA-37" now correctly appears on the power plan, but the designation "NTB-28" has not been removed

4. Please correct Service Load Total to reflect the project load changes. In that case, the total would read 1673A, not 1656A. The reason I am very particular about such totals is the practice of engineers to rely on previously sealed drawings for their design starting point, and the danger of accumulated error if we don't do all that we can to assure accuracy.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/21/2004 BETH GRANT OUT TO CUSTOMER Completed
07/21/2004 SUE REEVES REJECT SHELF Completed