Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM02457
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/02/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/09/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide energy code compliance calculations. Reference Section 101.2, International Energy Conservation Code 1998. 2. Provide calculations to show how the condensate lines have been sized. Show all pipe sizes and the slope of the pipe on the drawing. Reference Section 106.3.1, IMC 2000. 3. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC 2000. 4. Provide smoke detectors in the return air duct, upstream of any outside air connections, for all air distribution systems with a capacity greater than 2,000 CFM. Reference Section 606.1, IMC. |
| 06/09/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2000, for mercantile occupancy. 2. Provide rim elevation of next upstream sanitary manhole and first floor elevation. Determine need for backwater valve per Section 710.1, UPC 1994. 3. Provide equipment data for water heaters. Reference Section 103.2.3, UPC 1994. 4. Indicate the inverts of the new building sewer at its points of connection to the existing building sewer and to the HCS as well as its minimum slope. Reference Sections 718.1 and 718.3, UPC 1994. 5. Provide listing information for assemblies shown in details 5/P-2 and 6/P-2. Reference Sections 410.1 and 804.1, UPC 1994. |
| 06/09/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/14/2004 | Raul Palma | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/18/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/28/2004 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1. It appears that new Panels NTA and NTB are installed in a restroom, opening into the wall. Please clarify. 2. Restroom lights and fan are indicated on Ckt NTB-28 on power plan. Please account for such load on the panel schedule. 3. Rooftop maintenance receptacles are indicated on Ckt NTB-30 on power plan. Please account for such load on the panel schedule. 4. Load calculations for Panel NTA appear to total 25.4 KVA, 24.9 KVA, and 24.5 KVA respectively, and 212 A, 208 A, and 204 A respectively, for a total of 74 KVA. This would exceed the 200 A fused disconnect. Please note that according to NEC 220-13, only receptacles for which load was computed according to Sections 220-3 (b) (8) or 220-3 (b) (9) are subject to the demand factors in Table 220-13. 5. It appears that AFC at Panel NTA and NTB is 16,661 A and 15,216 A respectively, greater than the 10,000 A ratings. Granted that the fault current would face the impedance of the distance and connections between the Incoming Pull Section and the Junction Boxes, but it is doubtful that this would reduce the AFC at the panels to under 10K. Willing to discuss. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/29/2004 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 06/29/2004 | SUE REEVES | REJECT SHELF | Completed |