06/07/2004 DAN CASTRO ZONING REVIEW Approved
08/03/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM02439 DENIED 8/3/04

1. Present two sets of drawings for over-the-counter service.
2. Put project address on all sheets.
3. Provide disconnecting means for motor and controller per NEC 430 Part IX.
4. Indicate voltage and amperage capacity of sub-panel.
5. Provide panel schedules, including loading information, to demonstrate that panels are not overloaded.