Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM02430
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/09/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. An atmospheric vacuum breaker is not appropriate for use with an ice machine due to the valves downstream of the vacuum breaker. If the ice machine is equipped with pumps for water control, a reduced pressure backflow preventer will be required. Reference Section 603.2, UPC 1994. 2. Revise the water piping to coordinate with the revised water calculations. Coordinate the riser diagram with the plumbing plan. 3. Provide upper terminal cleanout for the pumped drain from the wash rack. Reference Section 710.7, UPC 1994. 4. Comment not addressed. Provide roof drainage calculations along with the sizes of the roof drains, overflows, and rain leaders. 5. Coordinate keynote #16 on sheet P1.1 with the current design and make keynote #20 legible. 6. Provide the civil drawing referenced in floor plan 1/P1.1 to show the routing of the building sewer. |
| 08/09/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the ventilation calculations for FCU-3 to comply with the requirements of Section 403.3.2, IMC 2000. |
| 08/10/2004 | GERRY KOZIOL | WWM | REVIEW | Denied | Needs to build public sewer. Need to show location/method of connection to public sewer. Cannot drain exterior wash rack to public sewer (need to remove from above fees when deleted from dwgs). Needs wastewater IWC review - Tom Tomchak, 579-5771. |
| 08/13/2004 | Doug Laakso | BUILDING-COMMERCIAL | REVIEW | Denied | .. T04CM02430 .. 8620 E TANQUE VERDE ROAD .. DGL .. 8/19/04 .. .. 2ND REVIEW S1. See prior comment #5 , revise calculations for masonry to reflect 2000 IBC criteria , as requested. S2. Provide on drawings soils requirements, showing extent of excavation and backfill, as well as , criteria for backfill soils and compaction for structure. S3. Indicate on drawings soils special inspection requirements. |
| 08/18/2004 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 08/19/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/19/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 08/19/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Approved |