Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM02417
Parcel: 120071980

Review Status: Completed

Review Details: REVISION

Permit Number - T04CM02417
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/13/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Grounding Electrode System needs to be established at Front Building if one is not already present. Second Building or Structure per NEC250.32. Show connection to such Grounding Electrode System, and specify sizing of Grounding Electrode Conductor.
2. Show utility Available Fault Current. Provide fault calculations at all pertinent parts of the system, and demonstrate that equipment has adequate fault current rating.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/15/2004 BETH GRANT OUT TO CUSTOMER Completed
12/15/2004 ANGIE SHOFFSTALL REJECT SHELF Completed