Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T04CM02415
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/13/2004 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Grounding Electrode System needs to be established at Front Building if one is not already present. Second Building or Structure per NEC250.32. Show connection to such Grounding Electrode System, and specify sizing of Grounding Electrode Conductor. 2. Show utility Available Fault Current. Provide fault calculations at all pertinent parts of the system, and demonstrate that equipment has adequate fault current rating. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/15/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |
| 12/15/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |