Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T04CM02391
Parcel: 113100010

Address:
1540 E GLENN ST

Review Status: Completed

Review Details: REVISION

Permit Number - T04CM02391
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/12/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM02391 DENIED 11/12/04
1. It appears that receptacle loads on Circuits P2-7 and P2-9 should be added to the panel schedule.
2. Electrical Load Summary allows a 40% demand factor. If the intent was to use NEC Table 220.20 for Kitchen Equipment, there is not such demand factor on this table.
3. Plans were originally approved on the condition that the Contractor was to provide the Engineer a 30-day demand reading. Using the results of such reading, provide final project load calculations.
11/12/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/18/2004 LISA LESNY OUT TO CUSTOMER Completed