Permit Number: T04CM02391
Parcel: 113100010

Address:
1540 E GLENN ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02391
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2004 JIM EGAN FIRE REVIEW Denied 1. Type 1 Kitchen Exhaust Hood with fire suppression system required.
2. Provide minium of one K-rated fire extinguisher in Kitchen.
05/27/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide information to show how the water piping has been sized. Indicate all loads on the ware piping.
2. Show total load and developed length for the gas piping.
05/27/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
05/27/2004 GERRY KOZIOL WWM REVIEW Approved
05/27/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
05/27/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide Type I hood for the range.
05/27/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
05/27/2004 ROBERT SHERRY WATER REVIEW Approved
06/14/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM02391 DENIED 5/27/04
1. Account for the following loads on panel schedule: Ckts 3, 5, 11, 13, 15, 2, 4, 6, 12, 14, 18, 20. Remarks indicate load, but there is no entry in the KVA column.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/14/2004 LISA LESNY OUT TO CUSTOMER Completed