Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM02391
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/27/2004 | JIM EGAN | FIRE | REVIEW | Denied | 1. Type 1 Kitchen Exhaust Hood with fire suppression system required. 2. Provide minium of one K-rated fire extinguisher in Kitchen. |
| 05/27/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide information to show how the water piping has been sized. Indicate all loads on the ware piping. 2. Show total load and developed length for the gas piping. |
| 05/27/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/27/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/27/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 05/27/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide Type I hood for the range. |
| 05/27/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 05/27/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/14/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM02391 DENIED 5/27/04 1. Account for the following loads on panel schedule: Ckts 3, 5, 11, 13, 15, 2, 4, 6, 12, 14, 18, 20. Remarks indicate load, but there is no entry in the KVA column. |