Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2004 GERRY KOZIOL WWM REVIEW Denied need to show location/method of connection to public sewer
(in Edison?) plumbing drawings show connection to south. If sharing private sewer, need joint use agreement.
07/12/2004 JIM TATE ENGINEERING REVIEW Denied DATE: July 12, 2004
ACTIVITY NUMBER: T04CM02380
PROJECT ADDRESS: 4342 E. Edison
PROJECT REVIEWER: James C. Tate, P.E., CFM

The following items must be revised or added to the Site Plan.

Resubmittal Required: Site Plan

GENERAL COMMENTS:

1. A Flood Use Permit is required prior to Site Plan approval.

2. Include estimated cut and fill quantities on the plan. Cut and fill quantities exceeding 50 cubic yards will require a Grading Plan and Permit. IBC Chapter 36

3. The Finish Floor Elevation (FFE) shown on the plans is incorrect. The Hydrology Report specifies that the FFE must be one foot above the 100-yr. peak water surface elevation. The Site Plan shows the FFE as one foot above existing grade. The Hydrology Report specifically calls out the FFE required for building 1 as 2459.1 NGVD-29. All appropriate sheets of the plan must specify this elevation and datum. An Elevation Certificate filled out by a registered land surveyor will be required to be returned to Development Services prior to final inspection of the structure. The FFE must be at or above 2459.1 NGVD-29 or final inspection will not be granted. All mechanical equipment (i.e. air conditioning compressors, hot water heaters, furnaces, etc) must also be placed at or above 2459.1 NGVD-29. This will also be shown on the Elevation Certificate. Correct the plans to show the proper FFE.
07/28/2004 Terry Stevens BUILDING-RESIDENTIAL REVIEW Denied TO MANY ITEMS MISSING TO BEGIN REVIEW

Final Status

Task End Date Reviewer's Name Type of Review Description
07/28/2004 BETH GRANT OUT TO CUSTOMER Completed