Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2004 JIM EGAN FIRE REVIEW Approved
06/09/2004 Daniel Castro ZONING REVIEW Denied COMMENTS: Please attach a response letter with the next
Submittal, which states how all Zoning Review Section comments Regarding the Land Use Code and Development Standards were Addressed.
CODE SECTION/ DEVELOPMENT STANDARD

1. Label and dimension future sight visibility triangles and future curb location. Per the Major Streets and Routes (MS&R) Plan, the face of future curb is located nine feet from the property line. (D.S. 2-02.2.1.A.10) (D.S. 2-02.2.1.A.21)

2. Provide a barrier (i.e. fence, wheel stop curbing, post barricades) to prevent vehicles from driving onto the unimproved portion of the site. It appears there is an opening next to the gate, which must be closed to vehicles. (D.S. 2-02.2.1.A.12) (D.S. 3-05.2.3.C.1)

3. Provide a barrier (i.e. curbing) along the east side of the proposed building location to prevent vehicles from encroaching onto the minimum required five (5) foot wide pedestrian refuge area. (D.S. 2-02.2.1.A.12) (D.S.3-05.2.3.C.1) (D.S. 3-05.2.2.B.1)

4. Where keynote 35 applies, the sidewalk must be concrete not asphalt. In addition, provide a concrete sidewalk where located next to the proposed sign location. The pedestrian path may be striped only where it crosses a PAAL. (D.S. 2-02.2.1.A.12) (D.S. 2-08.4.1) (D.S. 2-08.5.1.C)

5. Under the project data block on sheet G1 add the following note: Proposed land use is Vehicle Rental and Sales development designator "31", subject to LUC Section 3.5.9.5.A and .B.

6. Review of this plan by the Zoning Review Section may be done over the counter. Please contact Dan Castro to set an appointment.

If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.
06/10/2004 DAN CASTRO HANDICAP-SITE REVIEW Denied Where keynote 35 applies, the sidewalk must be concrete not asphalt. In addition, provide a concrete sidewalk where located next to the proposed sign location. The pedestrian path may be striped only where it crosses a PAAL. (D.S. 2-02.2.1.A.12) (D.S. 2-08.4.1) (D.S. 2-08.5.1.C)
06/14/2004 Joseph Linville LANDSCAPE REVIEW Denied 1) Revise the landscape plan to show the future sight triangles based on the MS&R right of way line. Revise the planting plan to locate plants which typically exceed thirty inches in height outside of the SVT. Plant #'s 3,4,5, may require relocation. DS 3-01.5.0

2) A six-foot high masonry wall is required along the east property line to screen the site from adjacent residentilly zoned property. LUC Table 3.7.2-I

3) Per DS 2-06.5.4.A.2, "Rigid irrigation pipes and flexible drip system irrigation lines under paved surfaces will be contained in pipe sleeves". Revise the site/landscape/irrigation plans to include provisions for sleeving where necessary.
06/14/2004 JOE LINVILLE NPPO REVIEW Approved Exception.
06/14/2004 PAUL MACHADO ENGINEERING REVIEW Denied To: Al J. Cornelio DATE: June 14, 2004
Architect
2957 W, Coriander Drive
Tucson, Arizona 85141

SUBJECT: Triple 'B' Auto Sales, 2333 S. Craycroft Road.
Site plan T04CM02371 (First Review)
T14S, R15E, Section 28

RESUBMITTAL REQUIRED: Site Plan and Drainage Statement.

The Site Plan (SP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. Show existing and future sight visibility triangles per 2-02.1.10.
3. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
4. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks.
5. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
6. Show Drainage patterns, proposed finished floor elevation(s) per D.S. 2-02.2.1.16.
7. List estimated cut and fill quantities per D.S. 2-02.2.1.17.
8. Dimensioned right-of-way, including any applicable Major Streets and Routes (MS from street monument lines etc. per D.S. 2-02.1.19.
9. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways and utility lines per D.S. 2-02.2.1.21.
10. Curb returns and Handi-cap ramps are required at the point of ingress/egress.
11. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. Please contact John Clark of Environmental Services for alley service at (520) 791-5543.
12. Show existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number.
13. List the owner/developer on the plans with the pertinent information.
14. Please show edge of pavement along perimeter of site.
15. The minimum width for a two way PAAL is 24'. Please revise the width of the North PAAL.
16. The PAAL distance should be measured form the edge of the travel lane, not to the property line when there is a fence.
17. Vertical curbs are required in the right-of-way, instead of extruded curbs. Please revise.
18. Key note no. 2 on sht. G2 should make reference to removing and replacing depressed curb with COT standard.
19. Keynote no. 6 on sht. G2 relocated gate on property, please show it's location.
20. Keynote no. 14 on sht. G2 references pavement transitions. Please show this on the plans.
21. Keynote no. 27 and 29 references extruded curb. Please revise to vertical curb.
22. Add note: "Depress all landscaped areas 6" maximum for water harvesting".

Drainage Statement:
1. A Drainage Statement is required. A DS is a brief description of drainage conditions applicable for a site which is not affected be 100-year flows of 100 cfs, or more, and is neither subject to detention requirements nor impacted by flows from a significant watercourse per S.M.D.D.F.M., chap. II, 2.1.3.
2. The content and format of the DS should follow S.M.D.D.F.M., chap. II, 2.1.3.
Show the project address on the cover of the Drainage Statement.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/2333 S. Craycroft Road