Permit Number: T04CM02347
Parcel: 13216022A

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T04CM02347
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/26/2004 GERRY KOZIOL WWM REVIEW Approved
06/22/2004 David Witt BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T04CM02347

6/22/04 1511 E. BERNARD #2

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


FLOOR PLANS:

1. PROVIDE ACCESS TO THE ATTIC SPACE. DESIGNATE THE LOCATION ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY ACCESSIBLE SPACE PER R807.

2. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED PER p2710 WITH CERAMIC TILE, OR A
LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2

STRUCTURAL PLANS:

1. SPECIFY LUMBER GRADE AND SPECIES.

2. PROVIDE MANUFACTURER'S CALCULATIONS AND DATA FOR PRE-FAB TRUSSES. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA.

SECTIONS - DETAILS - MISC. NOTES:

1. 1 / 2 ; PLEASE PROVIDE THE FOOTING THICKNESS.

2. 1 / 2 ; PROVIDE REINFORCEMENT AT THE TOP OF THE STEM. SEE R403.1.3.1 .

3. 2 / 2 ; JUSTIFY 8" CMU's ABILITY TO PROVIDE R-13.

4. 2 / 2 ; PLEASE RE-CHECK THE MODEL ENERGY CODE TABULATION. THE "HDD", HEATING DEGREE DAYS, SHOULD BE 2100. SEE SECTION 302.1 IN THE AMENDMENTS TO THE '98 INTERNATIONAL ENERGY CONSERVATION CODE. IT'S ON LINE.

5. 2 / 2 ; HOW DOES 9 ½" INSULATION PROVIDE R-30 ?

6. 2 / 2 ; HOW DOES THE CEILING GYPSUM BOARD COMPLY WITH TABLE R702.3.5 FOOTNOTE D ?

PLUMBING PLANS:

1. JUSTIFY THE 13 FIXTURE UNITS.

2. PLEASE RE-CHECK THE SIZING OF THE WATER DISTRIBUTION SYSTEM USING U.P.C. TABLE 6-4.

MECHANICAL PLANS:

1. NOTE ON PLANS: MECHANICAL SHALL COMPLY WITH CHAPTERS 12 - 24 2000 IRC.

2. PLEASE RE-CHECK THE SIZING OF THE RETURN AND SUPPLY AIRS, TO THE FIRST VENT FOR THE SUPPLY AIR, IN ACCORD WITH M1602 AND 1603 .




IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110

Final Status

Task End Date Reviewer's Name Type of Review Description
06/23/2004 TAMI ACHONG OUT TO CUSTOMER Completed
06/23/2004 ANGIE SHOFFSTALL REJECT SHELF Completed