Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2004 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the ventilation calculations using the occupant loads shown in Table 403.3, IMC 2000. Reference Sections 403.2, 403.3, and 403.3.2, IMC 2000. The appropriate occupancy classification for the customer area appears to be "Cafeteria, fast food", not "dining"; revise the calculations accordingly.
2. Show the hood support detail included with the structural calculations on the drawings. Reference Section 106.3.1, IMC 2000.
09/01/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Use the water fixture units shown in tables 6-3, and A-3 of the 1994 UPC for the fixture unit schedule. Include all fixtures, including existing fixtures, when calculating the total demand and determining pipe sizes. Reference Section 610.1, UPC 1994. Note the fixture units for water connections at the bottom of Table 6-3. Use the calculations shown on sheet P-2.0 to size the pipes.