Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM02341
Parcel: 137055200

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02341
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Denied 1) Handicapped watercloset shall be 16"- 18" max from wall.
06/04/2004 Jim Egan FIRE REVIEW Approved
06/10/2004 GERRY KOZIOL WWM REVIEW Approved
06/11/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC 1994.
2. Use the water and waste fixture units shown in tables 6-3, A-3, and 7-3 of the 1994 UPC for the fixture unit schedule. Include all fixtures, including existing fixtures, when calculating the total demand and determining pipe sizes. Reference Section 610.1, UPC 1994.
3. Show how the water heater is to be mounted above the mop sink and provide structural calculations. Confirm that the water heater complies with the access requirements of Section 511.0, UPC 1994 with AZ State amendments.
4. Show how the specified power venting system for the water heater is to be installed. Reference Section 524.0, UPC 1994.
5. The specified lavatory faucets are designed for a flow rate of 2.2 GPM. According to ARS Title 45, Chapter 1, Article 12, the maximum flow rate for lavatory faucets shall be no more than an average of one-half gallon of water per minute at a pressure of eighty PSI or they shall be equipped with a mechanism that causes the faucet to close automatically after delivering no more than one-fourth gallon of water. Reference Section 402.1, UPC 1994, as amended by the State of Arizona.
6. The mop sink is not to be connected to the grease interceptor. Reference Section H1, UPC 1994.
7. Provide upper terminal cleanout for floor sink located near cold pan. Reference Sections 707.4 and 707.5, UPC 1994.
8. Provide an upper terminal cleanout for floor sink located near 91" Chinese Oven. Reference Sections 707.4 and 707.5, UPC 1994.
9. Provide an upper terminal cleanout for floor sink located under the pot sink. Reference Sections 707.4 and 707.5, UPC 1994.
10. Provide an upper terminal cleanout for floor sink located under the vegetable sink. Reference Sections 707.4 and 707.5, UPC 1994.
11. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 704.4, IECC 1998.
12. Provide indirect waste for the pot and vegetable sinks only on the compartments used for sanitizing the dishes or utensils, or for washing ready-to-eat food. Reference Section 801.2, UPC 1994.
13. The indirect waste drain from the storage bin of an ice machine may not be combined with the cooling coil condensate drain (detail 9/P-4.0). Reference Sections 801.2 and 803.0, UPC 1994.
14. Provide protection of the trap seals for all floor drains. Reference Sections 1007.0 and 1007.1, UPC 1994, as amended by the State of Arizona.
15. Termination of the excess pressure relief from the water heater over a service sink is not approved location. Reference Section 608.5, UPC 1994.
06/11/2004 ROBERT SHERRY WATER REVIEW Approved
06/11/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the energy code analysis to use Tucson as the location for the project.
2. Provide calculations demonstrating adequate ventilation. Reference Sections 403.2, 403.3, and 403.3.2, IMC 2000.
3. Provide smoke detectors in the return air duct, upstream of any outside air connections, for all air distribution systems with a capacity greater than 2,000 CFM. Reference Section 606.1, IMC.
4. Coordinate the makeup airflow rates shown on the HVAC floor plan (Sheet M1.0, 5,000 CFM) with the airflow rates shown on the Make-up Air Unit Schedule (Sheet M-2.0, 6,000 CFM).
5. Provide structural calculations to show that the Type I hoods are adequately supported from the building structure. Reference Section 507.6, IMC 2000.
6. Revise the enclosing shaft for the grease duct to provide a minimum separation of 6" between the duct and the shaft. Reference Section 506.3.11, IMC 2000.
06/23/2004 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.Install disconnect switch @ ice machine10H. 2.Panel A cir.28 has two signs, one of which is 20amps. this load is too high for the circuits capacity. 3. Same comment as above only for circuit A-30. 4.Panel A cirrcuit 37,39 the 1.5 HP motor should draw 11 amps. 500 VA per phase appears too low. If this equip. only draws 1000watts total, as indicated @ panel schedule,the 15 amp fuse at disconnect is over sized. 5.Provide the available fault current at service equipment. 6. Provide the available fault current at panels A and B (provide calculations ). 7.Provide bracing requirements for panels A and B. 8.Panel loads and equipment schedule loads should not contradict each other.Clear up all descreprencies.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/28/2004 TAMI ACHONG OUT TO CUSTOMER Completed
06/28/2004 ANGIE SHOFFSTALL REJECT SHELF Completed