Permit Number: T04CM02328
Parcel: 13314816A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02328
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2004 JIM EGAN FIRE REVIEW Approved
05/25/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the water pipe sizes as shown on sheets P-1 (1-1/4" main) and P-2 (1-1/2" main).
2. Revise the water pressure calculations to include the pressure drops for the meter and the backflow preventer.
3. Correct the fixture unit calculations.
4. Clarify the direction of flow and the pipe sizing for the hot water. Show how the hot water recirculation is to function.
6. Provide insulation for the hot water piping.
7. Indicate the termination of the 4" waste line on the exterior of the building.
05/25/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
05/25/2004 ROBERT SHERRY WATER REVIEW Approved
05/25/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
05/25/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide energy code calculations.
05/26/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
05/26/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/27/2004 LLESNY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/27/2004 LISA LESNY OUT TO CUSTOMER Completed