Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM02327
Parcel: 133243700

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02327
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2004 JIM EGAN FIRE REVIEW Approved
05/25/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
05/25/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
05/26/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Correct waste fixture unit calculations.
2. Provide permanent access ladder to water heater. Reference Section 511.2, UPC 1994.
3. Show how the water piping was sized. Reference Section 610.1, UPC 1994.
05/26/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
05/26/2004 ROBERT SHERRY WATER REVIEW Approved
05/26/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify how the A/C units "share a common environment".
2. The ventilation requirement for Kitchens (25 cfm continuous) is applicable only for residences. Please revise.
3. Revise Mechanical Note #9 to comply with Section 606.2, IMC 2000.
06/02/2004 FFIGUER1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/02/2004 FFIGUER1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/02/2004 FFIGUER1 OUT TO CUSTOMER Completed