Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM02327
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/25/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 05/25/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 05/25/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 05/26/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Correct waste fixture unit calculations. 2. Provide permanent access ladder to water heater. Reference Section 511.2, UPC 1994. 3. Show how the water piping was sized. Reference Section 610.1, UPC 1994. |
| 05/26/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify how the A/C units "share a common environment". 2. The ventilation requirement for Kitchens (25 cfm continuous) is applicable only for residences. Please revise. 3. Revise Mechanical Note #9 to comply with Section 606.2, IMC 2000. |
| 05/26/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/26/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/02/2004 | FFIGUER1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 06/02/2004 | FFIGUER1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/02/2004 | FFIGUER1 | OUT TO CUSTOMER | Completed |