Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/25/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
05/25/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
05/25/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
05/26/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Correct waste fixture unit calculations. 2. Provide permanent access ladder to water heater. Reference Section 511.2, UPC 1994. 3. Show how the water piping was sized. Reference Section 610.1, UPC 1994. |
05/26/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify how the A/C units "share a common environment". 2. The ventilation requirement for Kitchens (25 cfm continuous) is applicable only for residences. Please revise. 3. Revise Mechanical Note #9 to comply with Section 606.2, IMC 2000. |
05/26/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/26/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/02/2004 | FFIGUER1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
06/02/2004 | FFIGUER1 | WWM | REVIEW | Needs Review |