05/25/2004 JIM EGAN FIRE REVIEW Approved
05/25/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
05/25/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
05/26/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Correct waste fixture unit calculations.
2. Provide permanent access ladder to water heater. Reference Section 511.2, UPC 1994.
3. Show how the water piping was sized. Reference Section 610.1, UPC 1994.
05/26/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify how the A/C units "share a common environment".
2. The ventilation requirement for Kitchens (25 cfm continuous) is applicable only for residences. Please revise.
3. Revise Mechanical Note #9 to comply with Section 606.2, IMC 2000.
05/26/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
05/26/2004 ROBERT SHERRY WATER REVIEW Approved
06/02/2004 FFIGUER1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/02/2004 FFIGUER1 WWM REVIEW Needs Review