Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T04CM02313
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/26/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/18/2004 | David Witt | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T04CM02313 6/21/04 125 S. CALLE EL CENTRO PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. 4. LIST THE SQUARE FOOTAGES FOR ALL THE FOLLOWING AREAS SEPARATELY ON THE DRAWINGS: - LIVABLE AREA - GARAGE - PORCH/PATIO COVERS - DECKS FLOOR PLANS: 1. PROVIDE A SIDE HINGED 3068 FOR EXITING. SEE R311 . 2. NOTE AND SPECIFY THAT SHOWER ENCLOSURES SHALL HAVE A MINIMUM FINISHED INTERIOR OF 1,024 SQUARE INCHES AND SHALL BE CAPABLE OF ENCOMPASSING A MINIMUM 30" CIRCLE PER UPC SEC. 410.0. ALL GLASS ENCLOSURES SHALL BE TEMPERED. ELEVATIONS: 1. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL VENTS NEEDED TO COMPLY. SECTIONS - DETAILS - MISC. NOTES: 1. 7 / A101 ; PLEASE PROVIDE WEEP HOLES FOR THE VENEER. SEE R703.7.6 . 2. 7 / A101 ; THE AIR SPACE IS REQUIRED TO BE 1" MINIMUM. SEE R703.7.4.2 . 3. 7 / A101 ; PLEASE PROVIDE A FLASHING FOR THE VENEER. SEE R703.7.5 . 4. 9 / A101 ; PLEASE PROVIDE COLLAR TIES OR CEILING JOISTS OR A RIDGE BEAM. SEE R802.3 . 5. 12 / A101 ; SIMPSON DOESN'T SHOW A VALUE FOR AN A35 IN THIS APPLICATION. PLEASE CONSIDER A H2.5 OR JUSTIFY THE A35 . 6. HOW IS THE ROOF VENTILATED? SEE R806 . 7. 9 / A101 ; JUSTIFY THE R-11 ROOF INSULATION. 8. 9 / A101 ; PROVIDE THE THICKNESS OF THE 3" X 3" LINTEL. MECHANICAL PLANS: 1. PROVIDE A WALKWAY AND A WORKING PLATFORM FOR THE ATTIC MOUNTED HEAT PUMP. SEE M1305.1.3 . 2. PROVIDE A SECONDARY CONDENSATE DRAIN FOR THE HEAT PUMP IN THE ATTIC. ELECTRICAL PLANS: 1. PROVIDE A LIGHT AND ARECEPTACLE FOR THE ATTIC MOUNTED HEAT PUMP. SEE M1305.1.3.1 AND E3801.11 . IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 1110 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/21/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 06/21/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |