Permit Number: T04CM02306
Parcel: 124050520

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02306
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/26/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved TO4EL02306 DENIED 5/25/04
1. Lights on Panel A lighting circuits total 4725 VA not 2137. Can not use NEC Table 220-3 (a) if load exceeds the minimum as computed from this Table.
2. Same concept as above on Panel B.
3. Add receptacle loads to calculations to both panels.
05/26/2004 GERRY KOZIOL WWM REVIEW Approved