Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/26/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | TO4EL02306 DENIED 5/25/04 1. Lights on Panel A lighting circuits total 4725 VA not 2137. Can not use NEC Table 220-3 (a) if load exceeds the minimum as computed from this Table. 2. Same concept as above on Panel B. 3. Add receptacle loads to calculations to both panels. |