Permit Number: T04CM02306
Parcel: 124050520

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02306
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2004 JIM EGAN FIRE REVIEW Approved
05/24/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/24/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
05/24/2004 ROBERT SHERRY WATER REVIEW Approved
05/24/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM02306 DENIED 5/24/04
1. Provide voltage, wattage, # of bulbs, catalogue cut numbers for lighting fixtures.
2. Add the water heaters to the plumbing schedule.
3. Provide a disconnect for the water heaters per NEC 422 Part C. Otherwise, certify that these units are cord-connected.
4. Rework load calculations applying 1.25% for continuous load and for the largest motor on each feeder.
5. 100A main on Panels A and B would not be on a branch circuit. Please clarify.
6. Speficy conduit and conductor sizes.
05/24/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/25/2004 DAN CASTRO ZONING REVIEW Approved
05/25/2004 ASHOFFS1 WWM REVIEW Needs Review
05/25/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/25/2004 ANGIE SHOFFSTALL OUT TO CUSTOMER Completed