Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM02306
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/24/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
05/24/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
05/24/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/24/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
05/24/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM02306 DENIED 5/24/04 1. Provide voltage, wattage, # of bulbs, catalogue cut numbers for lighting fixtures. 2. Add the water heaters to the plumbing schedule. 3. Provide a disconnect for the water heaters per NEC 422 Part C. Otherwise, certify that these units are cord-connected. 4. Rework load calculations applying 1.25% for continuous load and for the largest motor on each feeder. 5. 100A main on Panels A and B would not be on a branch circuit. Please clarify. 6. Speficy conduit and conductor sizes. |
05/24/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
05/25/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
05/25/2004 | ASHOFFS1 | WWM | REVIEW | Needs Review | |
05/25/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/25/2004 | ANGIE SHOFFSTALL | OUT TO CUSTOMER | Completed |