Permit Number: T04CM02201
Parcel: 11445262J

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02201
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2004 ROBERT SHERRY WATER REVIEW Approved
05/20/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the total amount of outside air for HP-2 to comply with the requirements of Section 403.2.3, IMC 2000.
2. Show that the restroom ventilation complies with Section 403.2.1, IMC 2000.
05/20/2004 GERRY KOZIOL WWM REVIEW Approved
05/20/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Revise fixture connection schedule to include the new hose bibb (in darkroom) and the ½" CW connection to the vacuum pump. Revise pipe sizes as required. Indicate if the hot water has been sized using Section 610.12 or Section 610.13, UPC 1994. Reference Section 610.1, UPC 1994.
2. Appliances to be directly connected to the water supply system (e.g. the vacuum pump and the darkroom equipment) that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994.
3. Provide listing information for the proposed water filter and show how it is to be installed. Reference Section 103.2.3, UPC 1994.
4. Clarify the size of the plumbing vent over OP. #2 - 2" or 2-1/2"?
5. Provide protection for the PVC pipe exposed to sunlight. Reference Section 313.5, UPC 1994.
05/24/2004 JIM EGAN FIRE REVIEW Approved
06/04/2004 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Completed
06/10/2004 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/10/2004 EGRANT1 OUT TO CUSTOMER Completed
06/10/2004 ANGIE SHOFFSTALL REJECT SHELF Completed