Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM02196
Parcel: 12801011A

Address:
302 S WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T04CM02196
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2004 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Passed
05/24/2004 JIM EGAN FIRE REVIEW Approved
06/04/2004 Doug Laakso BUILDING-COMMERCIAL REVIEW Denied T04CM02196 .. 302 S. WILMOT ROAD .. DGL .. 6/10/04

1ST REVIEW .. Comments #1 through #9 ..

1. Provide site plan, sealed by Bridge Engineer of Record , dimensionally tieing the bridge structure to two adjacent property lines , ( site plan to be "clean" with no prior approval stamps by public jurisdictions when submitted for this permit.).
2. Provide completed code review checklist ( see website www.ci.tucson.az.us/dsd ; forms and applications for downloadable form).
3. Provide completed commercial plan review submittal checklist, ( see website www.ci.tucson.az.us/dsd; forms and applications for downloadable form).
4. Provide copy of soils report for review.
5. Provide structural design per IBC or provide AASHTO code for review.
6. Provide Inspection Program per Uniform Administrative Code Section 302.5.
7. Special Inspection is required for :
1. Caissons
2. Foundation excavation and compaction 3. Concrete 4. Bolts in concrete 5. Reinforcing steel 6. Epoxy anchors 7. Prestressed concrete box girders 8. Lateral ties , detail 4/S5 9. Field welding 10. Installation of joint material 11. High - strength bolting
Additional Special Inspections may be required with completion of review.
8. Shop drawings are required for : 1. Precast box girders 2. Guardrail 3. Handrail.
9. Address accessibility of site, bridge and buildings on site, per IBC Chapters 11 and 34 and ANSI A117.1-1998 ed.

Questions , call Douglas Laakso City of Tucson Structural Plans Examiner at (520) 791-5550 x 1111.
06/14/2004 Doug Williams ENGINEERING REVIEW Approved Bridge location and elevations to be constructed in accordance with approved Grading Plan/Floodplain Use Permit conditions T03BU03106/T04OT00459.
06/22/2004 Daniel Castro ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/23/2004 BETH GRANT OUT TO CUSTOMER Completed
06/23/2004 ANGIE SHOFFSTALL REJECT SHELF Completed