Permit Number: T04CM02129
Parcel: 116120090

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T04CM02129
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2005 Doug Williams ENGINEERING REVIEW Denied SUBJECT: El Rio Parking
REVIEWER: Doug Williams
DATE: 7 January 2005
ACTIVITY NUMBERS: T04CM002129

SUMMARY: Engineering Division has reviewed the Site Plan received 8 December 2004. Approval is not recommended at this time. Please address the following comments:
1. The driveway apron may not be approved as proposed. The City of Tucson's Development Standard 3-01.3.2 C and Transportation Access Management Guidelines, Section 6.3.1(5) stipulate minimum 25' curb returns for driveways/PAALs intersecting Arterial roadways. Please revise the plan as necessary, demonstrating conformance with these standards, or provide written approval for the proposed design from Tucson Department of Transportation (TDOT) - Traffic Engineering Division.
2. Please depict additional finish grades along the proposed parking area perimeter, demonstrating conveyance of site drainage to the landscape areas and maintaining existing overall drainage patterns onsite (DS 2-02.2.1.16).
3. Include all easement recording information (docket and page) on the plan (Development Standard 2-02.2.1 A 20).
*** An over-the-counter review/approval may be arranged with me upon addressing/completion of the comments provided above. Please contact me at 791-5550, extension 1189 or via email at Doug.williams@tucsonaz.gov to arrange a time ***

Doug Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
12/13/2004 Andrew Connor LANDSCAPE REVIEW Approved
12/27/2004 PETER MCLAUGHLIN ZONING HC SITE REVIEW Denied See zoning review comments.
12/27/2004 Peter McLaughlin ZONING REVIEW Denied TO: John & Julieta Ferrel
3705 N. Nash Creek Ct.
Tucson, AZ 85745
(602) 954-9060

FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner
Development Services Dept.

PROJECT:
T04CM02129
New Barber Shop
1299 W. Speedway Blvd.
Site Plan Review (1st review)

TRANSMITTAL: December 27, 2004

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Add the existing use of the site to the project data. Rather than stating "tenant improvement", which is not a land use, list the specific use conducted on the property. For example if the use has been a house, state that the existing or previous use is "residential- single family dwelling". If this is a tenant improvement and the last approved use was a personal service/barber shop, provide copies of last approved site plan or certificate or occupancy for the use.
DS 2-02.2.1.A.31

2. Indicate the maximum slope of the van accessible handicap parking ramps and aisles to be provided on the drawing.
ANS/IBC

3. Provide specific maximum building heights of the building along each wall (north, south, east and west). It is unclear from the drawing which where the peak of the gabled roof is or which way it runs. Clarify on the drawing. Setbacks cannot be verified until building heights are specified.
DS 2-02.2.1.A.6

4. Dimension all building setbacks on the plan.
DS 2-02.2.1.A.7
LUC 3.2.6.4

5. According to the Assessors Office this site is made up of 2 lots, one being El Rio Park Lot 7, Blk 1 and the other being a portion of Lot 6, Blk 1. These lots must be combined so that the site is made up of one lot. Please provide documentation of combination with a recorded Covenant Regarding Use of Real Property, a copy of which is available at the Zoning Review Counter.
DS 2-02.2.1.A.2

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/11/2005 TAMI ACHONG OUT TO CUSTOMER Completed
01/11/2005 TAMI ACHONG REJECT SHELF Completed