Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM02129
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 05/12/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. A residential range located in a commercial establishment requires a Type 1 exhaust hood. reference Section 507.2.2, IMC 2000. 2. Show exhaust air flow rate for the restroom exhaust fan. |
| 05/12/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM02129 DENIED 5/12/04 1. Provide cut sheet for exterior lighting fixture. Plans Examiner needs to verify that such fixture is compliant with the Lighting Ordinance and that it is suitable to be installed outdoors. 2. Provide cut sheet for Fixture D. 3. Circuit SP-18 has load, such as TV, on plan view. Please account for load on panel schedule. 4. Receptacle outlets on the "north" side of middle room in plan view are not circuited. Please clarify. 5. Circuit MP-20 has load, such as receptacles, on plan view. Please account for load on panel schedule. 6. Circuit SP-17 has load, such as receptacle, on plan view. Please account for load on panel schedule. 7. Circuit MP-10 has lighting and fan in plan view, however receptacle is indicated on panel schedule. Please clarify. 8. Circuit MP-9 has receptacles in plan view, however lighting is indicated on panel schedule. Please clarify. 9. Circuit SP-15 has lighting in plan view, however oven exhaust is indicated on panel schedule. Please clarify. 10. This is an incomplete review. Please consider the above comments and double check the entire scope of work. |
| 05/12/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/12/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 09/08/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Needs Review | |
| 09/08/2004 | DAN CASTRO | ZONING | REVIEW | Needs Review | |
| 09/09/2004 | SREEVES1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/08/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |