Permit Review Detail
Review Status: Active
Review Details: RESUBMITTAL
Permit Number - T04CM02129
Review Name: RESUBMITTAL
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/10/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM02129 3/31/06 1. From the cut sheet submitted as Attachment A, this looks to be an incandescent fixture, and as such does not meet the requirements of 2000 IECC 805.5. 2. Please account for continuous loads and largest motors on panel schedules and calculations. There is "*" for the purpose, but no loads indicated. 3. TEP SR-510 does not assure 10,000 AFC. Please add the following note: "Contractor shall supply available fault current before final electrical clearance. All equipment shall have a fault current rating equal to or greater than that available at that point." 4. Riser Diagram shows 1?"C. Please clarify. |
| 04/10/2006 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 04/10/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/10/2006 | ANY | BUILDING-COMMERCIAL | REVIEW | Active |