Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM02088
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/20/2004 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Electrical is Code-compliant, but Mechanical specifications need to coordinate with Electrical classification of Heat Transfer Skid area as Class 1 Division 2. This applies to 15750-3 2.01 C 6. |
07/20/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The electrical hazard rating for the heat exchanger skid area has been changed to Class 1, Division 2. Revise the specifications for the motors and electrical enclosures as required. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/03/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
08/03/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |