Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM02088
Parcel: 13216600B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02088
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied Electrical is Code-compliant, but Mechanical specifications need to coordinate with Electrical classification of Heat Transfer Skid area as Class 1 Division 2. This applies to 15750-3 2.01 C 6.
07/20/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The electrical hazard rating for the heat exchanger skid area has been changed to Class 1, Division 2. Revise the specifications for the motors and electrical enclosures as required.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/03/2004 TAMI ACHONG OUT TO CUSTOMER Completed
08/03/2004 ANGIE SHOFFSTALL REJECT SHELF Completed