Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM02088
Parcel: 13216600B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02088
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2004 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Approved
07/01/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. "Since the conduit from MCC to New Panel C is to be run through the roof truss system, and since the area is Class 1 Division 2 up to the roof, it appears that the wiring method and conduit seals should be specified to comply with NEC 501-4 (b) and 501-5." This comment was made on the first submittal. From the response it is evident that this conduit run is indeed in a Class 1 Division 2 area. So please specify the conduit type and location of the seal with respect to the Class 1 Division 2 border indicated on the plans.
2. "The Heat Transfer Skid area has not been identified as a Classified location. However, such items as the CNG Pressure Transmitters, Pressure Switches, Level Switches, and Flow Switches are specified in Division 15 as meeting Class 1 Division 1 Group D requirements. Please verify whether the skid area needs classification itself, possibly Division 2 according to NEC 501(b), and whether the installation for Panel C, Circuit C-2,4,6, or any of the wiring associated with the PLC or the skid electrical equipment would be affected." This comment was made on the first submittal. Identify the extent of the classified area on the plans. Specify conduit and equipment type for all such items within such classified area, and location of all seals.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/12/2004 TAMI ACHONG OUT TO CUSTOMER Completed
07/12/2004 ANGIE SHOFFSTALL REJECT SHELF Completed