Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM02086
Parcel: 137055240

Review Status: Completed

Review Details: OTHER

Permit Number - T04CM02086
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved