Permit Number: T04CM02086
Parcel: 137055240

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02086
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM02086 DENIED 5/19/04
1. Provide accent lighting fixture schedule and cut sheet.
2. Provide Panel and circuit number for all electrical loads, such as accent lighting, pendant fixtures, and quad receptacles.
3. Provide panel load calculations.
05/19/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/19/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/19/2004 ROBERT SHERRY WATER REVIEW Approved
05/20/2004 JIM EGAN FIRE REVIEW Approved
05/21/2004 EGRANT1 WWM REVIEW Passed
05/21/2004 ANY BUILDING-COMMERCIAL REVIEW Approved